Control Cable

JZ-YSY

Brand: RR Kable

Technical Specifications

Feature Specification
Nominal Voltage: Uo / U 300 / 500V
Insulation Resistance: Min. 20 GΩ x cm
Temperature Range: Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
Minimum Bending Radius: Flexing 20 x cable ø. Fixed installation 6 x cable ø
Test Voltage: 4000V
Breakdown Voltage: Min. 8000V

Application

These cables are used as measuring and control cables in tool machinery, plant installation, power stations and in data equipment. The braided screen offers best possible protection against mechanical damage. The galvanised coating on the steel wire braiding not only helps protect against corrosion, but also notably improves the soldering performance.

Standard

Adapted to DIN VDE 0245, 0281, 0293, 0295.


Cable Construction

  •  Bare copper, fine wire conductors, to EN 60228 Cl.5.
  •  Core insulation of PVC TI2, EN 50363-3.
  •  Black Core with continuous white numbering to DIN VDE 0293.
  •  Green/Yellow earth core in outer layer (3 cores and above).
  •  Cores stranded in layers with optimal lay-length.
  •  Special PVC inner jacket.
  •  Galvanized steel wire screening.
  •  Special PVC outer jacket.
  •  Colour transparent (also available in grey).

Properties

  •  The clear transparent PVC outer sheath accentuates the optical view of the galvanized steel wire braid
  •  PVC self-extinguishing and flame retardant according to EN 60332-1-2
  •  JZ-YSY Grey(RAL 7001) is also available in oil resistant variant as JZ-YSY OR. The outer sheath provided here is of special PVC TM5 to BS EN 50363 -4.1.

Cabel Design Parameters

Please complete the part numbers for these cables by adding the suffix (in place of ‘z’) for the sheath colour required :

3 – grey (RAL 7001), 6 – transparent. For oil resistant sheath (grey), kindly add ‘OR’ after the part nos.

Related Product

RR Kable

JZ-500

  • Uo / U 300 / 500V
  • Min. 20 GΩ x cm
  • Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
RR Kable

Control Cable (IS 694)

  • IS 694 marked, FIA/TAC
  • Electrolytic grade annealed copper Class-5 as per IS 8130, having uniform resistance properties
  • All black colour cores with continous white numbering, gn-yl core on outer most layer for earth if applicable
RR Kable

JZ-CY

  • Uo / U 300 / 500V
  • Min. 20 GΩ x cm
  • Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
RR Kable

JZ-YCY

  • Uo /U 300 / 500V
  • Min. 20 GΩ x cm
  • Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
RR Kable

JZ-YSY

  • Uo / U 300 / 500V
  • Min. 20 GΩ x cm
  • Flexing -5°C to +70°C. Fixed installation -30°C to +70°C
RR Kable

JB-YCY

  • Uo / U 300 / 500V up to 1.5 mm². Uo / U 450 / 750V for 2.5 mm² and above
  • Min. 20 GΩ x cm
  • Flexing -5°C to +70°C. Fixed installation -30°C to +70°C